Lessons From an Outbreak of Legionnaires’ Disease on a Hematology-Oncology Unit

Published online by Cambridge University Press:  06 December 2016

Louise K. Francois Watkins*
Affiliation:
Epidemic Intelligence Service Program, Atlanta, Georgia
Karrie-Ann E. Toews
Affiliation:
Centers for Disease Control and Prevention, Atlanta, Georgia
Aaron M. Harris
Affiliation:
Centers for Disease Control and Prevention, Atlanta, Georgia
Sherri Davidson
Affiliation:
Alabama Department of Public Health, Montgomery, Alabama
Stephanie Ayers-Millsap
Affiliation:
Jefferson County Department of Health, Birmingham, Alabama
Claressa E. Lucas
Affiliation:
Centers for Disease Control and Prevention, Atlanta, Georgia
Brian C. Hubbard
Affiliation:
Centers for Disease Control and Prevention, Atlanta, Georgia
Natalia A. Kozak-Muiznieks
Affiliation:
Centers for Disease Control and Prevention, Atlanta, Georgia
Edward Khan
Affiliation:
Jefferson County Department of Health, Birmingham, Alabama
Preeta K. Kutty
Affiliation:
Centers for Disease Control and Prevention, Atlanta, Georgia
*
Address correspondence to Louise K. Francois Watkins, 1600 Clifton Rd. NE, Mailstop C-09, Atlanta, GA 30329 (hvu9@cdc.gov).
Rights & Permissions [Opens in a new window]

Abstract

OBJECTIVES

To define the scope of an outbreak of Legionnaires’ disease (LD), to identify the source, and to stop transmission.

DESIGN AND SETTING

Epidemiologic investigation of an LD outbreak among patients and a visitor exposed to a newly constructed hematology-oncology unit.

METHODS

An LD case was defined as radiographically confirmed pneumonia in a person with positive urinary antigen testing and/or respiratory culture for Legionella and exposure to the hematology-oncology unit after February 20, 2014. Cases were classified as definitely or probably healthcare-associated based on whether they were exposed to the unit for all or part of the incubation period (2–10 days). We conducted an environmental assessment and collected water samples for culture. Clinical and environmental isolates were compared by monoclonal antibody (MAb) and sequence-based typing.

RESULTS

Over a 12-week period, 10 cases were identified, including 6 definite and 4 probable cases. Environmental sampling revealed Legionella pneumophila serogroup 1 (Lp1) in the potable water at 9 of 10 unit sites (90%), including all patient rooms tested. The 3 clinical isolates were identical to environmental isolates from the unit (MAb2-positive, sequence type ST36). No cases occurred with exposure after the implementation of water restrictions followed by point-of-use filters.

CONCLUSIONS

Contamination of the unit’s potable water system with Lp1 strain ST36 was the likely source of this outbreak. Healthcare providers should routinely test patients who develop pneumonia at least 2 days after hospital admission for LD. A single case of LD that is definitely healthcare associated should prompt a full investigation.

Infect Control Hosp Epidemiol 2017;38:306–313

Type
Original Articles
Creative Commons
Creative Common License - CCCreative Common License - BY
This is an Open Access article, distributed under the terms of the Creative Commons Attribution licence (http://creativecommons.org/licenses/by/4.0/), which permits unrestricted re-use, distribution, and reproduction in any medium, provided the original work is properly cited. All rights reserved.
Copyright
© 2016 by The Society for Healthcare Epidemiology of America. All rights reserved

Legionnaires’ disease (LD) is a severe form of pneumonia caused by gram-negative Legionella bacteria.Reference McDade, Shepard, Fraser, Tsai, Redus and Dowdle 1 Legionella species are ubiquitous in natural aquatic environments,Reference Rowbotham 2 but illness typically occurs when contaminated droplets of aerosolized water from a human-made source are inhaled or aspirated. Most reported cases are community acquired, but at least 7% are healthcare associatedReference Dooling, Toews and Hicks 3 ; mortality in healthcare-associated LD is higher than in community-acquired cases and ranges from 13% to 46%.Reference Benin, Benson and Besser 4 Reference Stocker, Brodhun and Buchholz 6 Patients with immune compromise are at increased risk of developing LD if exposed to Legionella Reference Hilbi, Jarraud, Hartland and Buchrieser 7 and may experience increased severity and fatal outcomes,Reference Wickramasekaran, Sorvillo and Kuo 8 , Reference Wang, Chin and Liu 9 making prompt detection of outbreaks in healthcare facilities particularly important.

In May 2014, the Alabama Department of Public Health (ADPH) notified the Centers for Disease Control and Prevention (CDC) of 8 LD cases diagnosed since March 2014 among inpatients on a single hematology-oncology unit at an Alabama hospital. In this report, we characterize the outbreak, discuss contributing factors, and identify lessons learned.

METHODS

Outbreak Setting

The outbreak occurred at a medical center that serves as a hematology-oncology referral center for patients throughout the state. The hematology-oncology unit contains 27 single-occupancy patient rooms and occupies half a floor in the affected building, a 9-story building with independent water and ventilation systems. Although construction on most of the affected building was completed in 2009, construction of the hematology-oncology unit was not completed until December 2013; patients were first admitted on February 20, 2014.

Case Definitions

A healthcare-associated LD case was defined as clinically or radiographically confirmed pneumonia and a positive urinary antigen test and/or respiratory culture for Legionella in a person with exposure to the hematology-oncology unit after February 20, 2014, and during the typical incubation period of 2–10 days prior to symptom onset. Definitely healthcare-associated LD cases occurred in patients admitted to the unit for the entire incubation period and in persons with a respiratory isolate identical to an environmental isolate from the unit determined by molecular sequence typing. Most likely, healthcare-associated cases occurred in persons with exposure to the unit for a portion of the incubation period with no clinical isolate.

Case Finding and Chart Review

To identify potential LD cases, hospital laboratory records were reviewed for all respiratory cultures and urine antigen tests positive for Legionella since February 20, 2014. No Legionella-specific paired serology, direct fluorescence antibody testing, or PCR-based testing was performed during this period. In addition, ADPH reviewed all reported LD cases in the state since the unit opened for possible connection to the hospital. Charts of patients with a positive Legionella lab test and exposure to the hematology-oncology unit were reviewed for clinical and epidemiological characteristics using a standardized form.

Environmental Assessment and Sampling

Environmental assessments of the affected building and its environs were performed. Infection prevention staff and facility engineers participated in open-ended interviews about Legionella prevention practices. When the affected building opened in 2009, the hospital had an established Legionella water management program consisting of annual environmental sampling. However, the program did not contain key elements from legionellosis prevention guidelines, 10 including routine testing of other water parameters (eg, temperature, pH, and chlorine levels) or clinician education.

Based on the environmental assessment, 64 bulk water samples (1 liter each) and biofilm swab samples were collected from 30 locations for Legionella culture according to established methods. 10 Sampled sites included the point of entry for municipal water flowing into the affected building, water circulating in the 140°F supply and 120°F return loops of the central water system, and point-of-use faucets in patient care areas in the hematology-oncology unit and other units in the affected building. Water temperature, pH, and total chlorine residual were measured at sites throughout the potable water system. Records of all previous environmental sampling for Legionella in the affected building from January 2010 through May 2014 were also reviewed.

Laboratory Methods

All patient isolates and environmental samples were processed at the CDC’s Pneumonia Response and Surveillance Laboratory according to previously established methods.Reference Kozak, Lucas and Winchell 11 , 12 Monoclonal antibodies (MAbs) were used to determine whether Legionella isolates were L. pneumophila serogroup 1 (Lp1) and whether they reacted with MAb2, a marker of enhanced virulence potential.Reference Dournon, Bibb, Rajagopalan, Desplaces and McKinney 13 , Reference Kozak, Benson and Brown 14 Multiplex polymerase chain reaction (PCR) was used to test whether non-Lp1 isolates were L. pneumophila or belonged to other Legionella species.Reference Benitez and Winchell 15 Finally, 7-gene sequence-based typing (SBT) was performed on all Lp1 clinical isolates and a subset of 9 Lp1 environmental isolates as previously described.Reference Gaia, Fry, Harrison and Peduzzi 16 , Reference Ratzow, Gaia, Helbig, Fry and Luck 17 For non-pneumophila isolates, mip gene sequencing was undertaken to determine the species. L. pneumophila isolates from (non-Lp1) serogroups underwent slide agglutination and direct fluorescence antibody testing to determine the serogroup.

Ethics Review

The CDC reviewed plans for this investigation which was determined to be a non-research study because it constituted an urgent public health response.

RESULTS

Epidemiological Results

In total, 10 cases were associated with this outbreak, with symptom onset dates between March 8 and June 3, 2014. Of these 10 cases, 9 cases were identified among the 443 inpatients who were admitted to the hematology-oncology unit for at least 12 hours between the unit opening and the beginning of the investigation. Furthermore, 1 case occurred in a visitor who stayed overnight with a relative in the same unit (Figure 1). No cases were identified among patients with exposure to other parts of the affected building or among inpatients admitted to other buildings on the hospital campus.

FIGURE 1 Epidemic curve of healthcare-associated cases of Legionnaires’ disease (n=10) by week of symptom onset. ADPH, Alabama Department of Public Health. Reference McDade, Shepard, Fraser, Tsai, Redus and Dowdle 1 All cases were reported to the respective local health departments within 1 week of positive test results.

Case characteristics are summarized in Table 1. Of the 10 cases, 6 (60%) were classified as definitely healthcare associated, and 4 (40%) were classified as probably healthcare associated. All case patients had at least 1 medical risk factor; 1 patient had a history of a lung transplant and chronic neutropenia, the visitor had a diagnosis of chronic obstructive pulmonary disease, and the remaining 8 patients had active leukemia. A single patient was originally admitted with a new diagnosis of acute myelogenous leukemia (AML) and received the first oncologic treatment during this admission to the hematology-oncology unit.

TABLE 1 Characteristics of Legionnaires’ Disease Case Patients (n=10) With Exposure to a Hospital Hematology-Oncology Unit — Alabama, 2014.

NOTE. ICU, intensive care unit.

a Data were available for all 10 case patients except where indicated.

b Ethnicity data were available for 3 case patients.

c Defined as a chest x-ray or computed tomography scan with evidence of a new consolidation or infiltrate.

d Respiratory cultures were obtained for 7 case patients.

e Clinical risk factors include chronic lung disease, immune suppression from a medical condition (eg, diabetes, cancer, kidney failure), and immune suppression from medications.

f Alcohol abuse was considered to be present if it was documented in the chart under “past medical history” or if social history indicated >14 alcoholic drinks/week (women) or >21 alcoholic drinks per week (men).

g At any point during the admission where exposure to Legionella likely occurred.

h Defined as white blood cell count (WBC)<4,000 cells/µL; data were available for the 9 inpatients only, and of these, 8 patients had a white cell differential available and all were neutropenic, with median absolute neutrophil count of 22 cells/µL (range, 0–43).

i During the 10 days prior to symptom onset.

j Excludes antibiotics with no known in vivo activity against Legionella species (eg, β-lactams, aminoglycosides, vancomycin); 1 case patient was prescribed an antibiotic with potential activity against Legionella (trimethoprim [160 mg]-sulfamethoxazole [800 mg], 1 tablet 3 days a week), and she received 2 doses over 3 days in the 10 days prior to her symptom onset.

k Systemic steroids included prednisone, methylprednisolone, hydrocortisone, and dexamethasone.

l During the 2–10 days prior to symptom onset.

m Procedures included bone marrow biopsy (n=2), Hickmann catheter placement (n=1), and lumbar puncture (n=1).

Figure 2 shows the probable window of case exposure to Legionella (2–10 days prior to symptom onset), the dates of exposure to the hematology-oncology unit, and the dates of Legionella testing. The median time between symptom onset and Legionella testing was 8.5 days (range, 0–65 days). The outbreak was first recognized by the hospital laboratory and infection prevention team during the first week of May, at which time all hematology-oncology unit clinicians were notified (treating clinicians were notified of test results as they became available). Subsequent testing of patients with exposure to the affected building was performed at the discretion of individual clinicians; 24 of the 89 total inpatients exposed to the unit after outbreak recognition had been tested for Legionella at the time of the investigation. Patients who tested positive all had healthcare-associated pneumonia consistent with LD.

FIGURE 2 Probable incubation period (2–10 days prior to symptom onset), exposure to hematology-oncology unit, and positive Legionella test collection date by case patient (n=10).

Environmental Results

The affected building received water directly from the municipal water supply. Water was distributed throughout the building via 3 independent water risers supplying floors 1–3, 4–7 (including the hematology-oncology unit), and 8–9, respectively. Each patient room was single occupancy and was equipped with 2 sinks and a shower, and each unit had several sinks for staff use as well as an ice machine connected to the building’s water system. Further assessment of the hospital campus did not identify any nearby cooling towers, and the affected building did not contain whirlpool spas, water-birth facilities, patient bathtubs, decorative fountains, or other obvious sources of aerosolized water.

At points of use, the median hot water temperature after 2 minutes was 102.5°F (range, 92.5°F–112.4°F) and median pH was 7.5 (range, 7.0–8.5). The total chlorine in the municipal water at the entrance to the affected building was measured at 1.2 ppm (a level thought to inhibit the growth of Legionella), but the chlorine residual in the cold water dropped at most points of use, including to undetectable levels (<0.1 ppm) in some hematology-oncology unit rooms. Total chlorine in the hot water system supplying the unit was undetectable at 7 of 12 points of use.

Records from the Legionella water management program revealed that no Legionella species were isolated from the affected building until 2012, when Legionella species were isolated from samples taken on floors 1, 8, and 9 (supplied by separate water risers). In 2013 and 2014, Legionella species including Lp1 were detected at sites supplied by the same water riser as the hematology-oncology unit, even though no testing was performed on the unit itself. Following identification of the outbreak by the hospital, additional sampling followed by superheating and flushing took place on May 7–9. The referral laboratory where these samples were cultured forwarded 5 isolates from floors 4–6 to the CDC for subtyping.

Laboratory Results

Legionella species were cultured from 21 of 30 sites (70%) sampled during the environmental investigation; legionellae were not recovered from the 2 sites that were not supplied by the second water riser (a sink in a neighboring building and water entering the affected building). Of 10 point-of-use sites on the hematology-oncology unit, 9 (90%) showed Legionella growth (Figure 3), including all 4 of the case patient rooms sampled. Multiple species of Legionella were recovered, including Lp1, Lp13, and several non-pneumophila strains; however, Lp1 was identified at all sites showing Legionella growth. MAb testing identified both MAb2-positive and MAb2-negative Lp1 strains; 15 sites (72%) showed both types. Sequence typing was performed on 9 Lp1 isolates from 7 sites (7 of these isolates [78%] were MAb2-positive), on the 3 Lp1 clinical isolates, and on 3 Lp1 isolates collected from the affected building prior to the investigation. All Lp1 isolates had identical sequence type results (ST36).

FIGURE 3 Schematic of the hematology-oncology unit showing the sites of positive environmental sampling results (figure not to scale). Of 27 rooms, 9 were occupied by case patients for at least 1 night; Legionella species were isolated from points-of-use in each of the 4 case patient rooms from which samples were obtained.

Outbreak Response and Remediation

Water restrictions (limiting contact with the affected building’s potable water to washing visibly soiled hands) were implemented on May 25 for patients, visitors, and staff. Bottled water was provided for drinking and hygiene activities, and alcohol-based hand sanitizer was provided for routine hand cleansing; distilled water was routinely used with respiratory equipment prior to this outbreak. These restrictions were lifted once 0.2-μm point-of-use filters were obtained for all sinks, showerheads, and ice machines in the affected building. Remediation of the potable water system was initiated once environmental samples were obtained and consisted of superheating each of the 3 water-riser systems to 160°F, flushing, and hyperchlorination (a chlorine injection system was installed for emergency remediation). Ongoing monitoring of chlorine at points of use and follow-up sampling with subsequent remediation as needed were advised. Only 1 case occurred with symptom onset after the implementation of water restrictions and remediation, but her incubation period overlapped with the period before these interventions.

DISCUSSION

Our investigation strongly implicates the potable water system as the likely source of this outbreak; Lp1 strains isolated from water on the unit were indistinguishable from all 3 clinical specimens by SBT. Strain, environmental, and host factors likely contributed to the outbreak. ST36 is considered highly virulent based on its association with previous outbreaks, including the landmark LD outbreak in Philadelphia in 1976.Reference McDade, Shepard, Fraser, Tsai, Redus and Dowdle 1 , Reference Kozak-Muiznieks, Lucas and Brown 18 Environmental risk factors for contamination of the potable water system included water temperatures favoring Legionella amplification (77–108°F 10 , Reference Wadowsky, Yee, Mezmar, Wing and Dowling 19 21 ), inadequate biocide (eg, low chlorine 21 Reference Marrie, MacDonald, Clarke and Haldane 23 ), the recent internal construction on the unit,Reference Mermel, Josephson, Giorgio, Dempsey and Parenteau 24 Reference Stout, Brennen and Muder 26 and probable water stagnation in the distal piping and water fixtures in the weeks between completion of the unit’s plumbing and its opening. 21 These findings are consistent with a recent review of environmental factors contributing to outbreaks of legionellosis.Reference Garrison, Kunz and Cooley 27 Host factors also contributed. While any hospitalized patient should be considered at increased risk for LD, hematology-oncology patients may be at comparatively greater risk based upon immune compromise resulting from active leukemia, recent chemotherapy, and systemic steroid use.Reference Hilbi, Jarraud, Hartland and Buchrieser 7 , Reference Landau, Rezvak, Shtalrid and Resnitzky 28 , Reference Kaya, Erginel, Metintas, Ustuner, Ucgun and Ozdemir 29 Interestingly, case patients had strikingly similar clinical histories: 8 (80%) had active leukemia (including 7 with AML), all had received chemotherapy during their admission and were severely neutropenic. No patients received antibiotics recommended for the treatment of legionellosisReference Mandell, Wunderink and Anzueto 30 in the 10 days prior to symptom onset, but 7 (70%) had systemic steroid exposure during the same interval. The single visitor also had risk factors for LD, underscoring the importance of considering visitors when implementing prevention measures in a healthcare-associated outbreak.

Although >25% of patients admitted to the hematology-oncology unit were ultimately tested for Legionella, all patients who tested positive by urine antigen or culture had symptoms of healthcare-associated pneumonia within 2–10 days of exposure to the unit (ie, no “subclinical” or “asymptomatic” cases were observed). Furthermore, 2 patients tested positive after symptom resolution, which is consistent with reports of patients shedding Legionella antigen in the urine for months after a severe infection.Reference Kohler, Winn and Wheat 31 Patients with immune compromise may be more likely to experience prolonged antigen excretion.Reference Sopena, Sabria and Pedro-Botet 32 , Reference Higa, Fujita, Koide, Haranaga and Tateyama 33 Our findings support the consideration of a positive urine antigen test as highly specific for clinical illness. 34

No cases occurred with exposure exclusively after the implementation of water restrictions and installation of 0.2 μm point-of-use filters. Although it is not possible to distinguish the individual contribution of the filters to the resolution of this outbreak, the results of this investigation are consistent with previous reports that 0.2-μm point-of-use filters are effective at preventing the passage of Legionella species.Reference Salvatorelli, Medici, Finzi, De Lorenzi and Quarti 35 , Reference Baron, Peters, Shafer, MacMurray and Stout 36 Current guidelines 37 recommending water restrictions explicitly for patients on transplant units should be broadened to include all hospitalized patients in an outbreak setting.

Prompt recognition of LD outbreaks in healthcare settings is essential to protecting vulnerable patients. Multiple factors contributed to the 2-month delay in the detection of this outbreak, illustrating several important lessons for health departments, healthcare facilities, and clinicians. First, although the hospital had a Legionella water management program, providers were not routinely notified of positive environmental testing results. Consequently, clinicians may have been less likely to include diagnostic testing for LD in their initial management of patients with healthcare-associated pneumonia, resulting in a delay in diagnosis and ineffective empiric antibiotic treatment. Regular clinician education should be an integral part of a hospital’s Legionella water management program; a toolkit to help facilities develop an effective program is now available on the CDC website. 38 The CDC recommends Legionella testing for patients who develop pneumonia at least 48 hours after admission to a healthcare facility, 37 particularly when Legionella species have been previously identified in the potable water. Testing by both urine antigen test and respiratory culture is recommended to maximize case detection.Reference Murdoch 39 Second, some cases were misclassified as community acquired rather than healthcare associated at local health departments.

Review of interview documentation revealed that several case patients answered questions about symptom onset based upon their leukemia rather than LD. When interviewing patients with comorbidities, it is important to clarify the reason for the interview and to attempt to identify the onset of respiratory signs and symptoms because other symptoms of LD (nausea, malaise, fever) may not be sufficiently specific. Third, the report of a single definitely healthcare-associated LD case (eg, a patient with continuous exposure to a healthcare facility during the entire 10-day incubation period) should prompt public health action. The CDC recommends responding to a single definitely healthcare-associated LD case with a full investigation. Finally, public health surveillance should include reporting requirements to reliably identify when 2 reported cases share a common exposure to a healthcare facility. In this outbreak, all cases were reported to the appropriate local public health authorities, but their common exposure to a single hospital was initially missed. This may have occurred in part because the case patients were residents of multiple jurisdictions, consistent with the hospital’s statewide patient population. Furthermore, when a healthcare facility or laboratory identifies 2 or more cases with a common exposure, public health authorities should be notified immediately.

This investigation has several limitations. First, by limiting our case definition to laboratory-confirmed cases, we could not quantify the scope of the outbreak. We did not attempt to identify “possible” cases (patients who developed pneumonia following exposure to the affected building but who did not undergo timely Legionella testing), as healthcare-associated pneumonia commonly occurs among hematology-oncology inpatients due to multiple etiologies. In addition, while we hypothesize that clinical features such as leukemia, neutropenia, and steroid use contributed to increased risk for LD, we did not collect data on a “control” population to assess the magnitude of risk posed by various clinical factors. Finally, although transmission appeared to cease after the implementation of water restrictions and filter placement, it is not possible to determine the individual contribution of these measures, given that other remediation efforts were implemented simultaneously.

In conclusion, we describe an outbreak of healthcare-associated LD among a vulnerable patient population. Water restrictions and point-of-use filters may help to halt transmission, and their immediate implementation should be considered to protect susceptible patients when potable water is a suspected outbreak source. Healthcare facilities should employ a Legionella water management program and should follow established prevention guidelines for building water systems, 10 with attention to key requirements for routine water quality monitoring, corrective action, and documentation. The program should include clinician education regarding the presence of Legionella species in the potable water system. 38 To improve the timeliness of outbreak detection in healthcare facilities, we recommend prompt reporting of healthcare-associated legionellosis to public health authorities, followed by investigation when ≥2 cases share a common facility exposure or when a single case has continuous facility exposure throughout the entire 2–10-day incubation period.

ACKNOWLEDGMENTS

We gratefully acknowledge the contributions of the following individuals to this investigation: Allison Albert, Bruce Braden, Ellen Brown, Bernard Camins, Craig Corwin, Laurel Garrison, Russell Griffin, Lauri Hicks, Jasen Kunz, Rachel Lee, Cindy Lesinger, Mary McIntyre, Jim McVay, Jeffrey Mercante, Kelly Stevens, Jonas Winchell, and Anisa Xhaja. The findings and conclusions in this report are those of the authors and do not necessarily represent the official position of the Centers for Disease Control and Prevention.

Financial support: No financial support was provided relevant to this article.

Potential conflicts of interest: All authors report no conflicts of interest relevant to this article.

Footnotes

PREVIOUS PRESENTATIONS: Findings from this investigation were presented at the 64th Annual Epidemic Intelligence Service Conference in Atlanta, Georgia (April 20, 2015), at the 2015 Council of State and Territorial Epidemiologists Conference in Boston, Massachusetts (June 17, 2015), and at the International Conference of Emerging Infectious Diseases 2015, Atlanta, Georgia (August 26, 2015).

References

REFERENCES

1. McDade, JE, Shepard, CC, Fraser, DW, Tsai, TR, Redus, MA, Dowdle, WR. Legionnaires’ disease: isolation of a bacterium and demonstration of its role in other respiratory disease. N Engl J Med 1977;297:11971203.Google Scholar
2. Rowbotham, TJ. Preliminary report on the pathogenicity of Legionella pneumophila for freshwater and soil amoebae. J Clin Pathol 1980;33:11791183.Google Scholar
3. Dooling, KL, Toews, KA, Hicks, LA, et al. Active bacterial core surveillance for legionellosis—United States, 2011–2013. MMWR Morb Mortal Wkly Rep 2015;64:11901193.Google Scholar
4. Benin, AL, Benson, RF, Besser, RE. Trends in Legionnaires’ disease, 1980–1998: declining mortality and new patterns of diagnosis. Clin Infect Dis 2002;35:10391046.Google Scholar
5. Dominguez, A, Alvarez, J, Sabria, M, et al. Factors influencing the case-fatality rate of Legionnaires’ disease. Int J Tuberc Lung Dis 2009;13:407412.Google Scholar
6. Stocker, P, Brodhun, B, Buchholz, U. Nosocomial Legionnaires’ disease—results from the analysis of Germany’s surveillance data; 2004–2006 [in German]. Bundesgesundheitsblatt, Gesundheitsforschung, Gesundheitsschutz 2009;52:219227.Google Scholar
7. Hilbi, H, Jarraud, S, Hartland, E, Buchrieser, C. Update on Legionnaires’ disease: pathogenesis, epidemiology, detection and control. Mol Microbiol 2010;76:111.Google Scholar
8. Wickramasekaran, RN, Sorvillo, F, Kuo, T. Legionnaires’ disease and associated comorbid conditions as causes of death in the U.S., 2000–2010. Public Health Rep 2015;130:222229.CrossRefGoogle ScholarPubMed
9. Wang, LS, Chin, TD, Liu, C. Nosocomial Legionnaires’ disease. Zhonghua yi xue za zhi 1989;44:242248.Google Scholar
10. ANSI/ASHRAE Standard 188-2015: Legionellosis: risk management for building water systems. American Society of Heating, Refrigerating and Air-Conditioning Engineers; 2015.Google Scholar
11. Kozak, NA, Lucas, CE, Winchell, JM. Identification of Legionella in the environment. Methods Mol Biol 2013;954:325.Google Scholar
12. Procedures for the recovery of Legionella from the environment. Centers for Disease Control and Prevention website. http://www.cdc.gov/legionella/specimen-collect-mgmt/procedures-manual.pdf. Published 2005. Accessed February 24, 2016.Google Scholar
13. Dournon, E, Bibb, WF, Rajagopalan, P, Desplaces, N, McKinney, RM. Monoclonal antibody reactivity as a virulence marker for Legionella pneumophila serogroup 1 strains. J Infect Dis 1988;157:496501.Google Scholar
14. Kozak, NA, Benson, RF, Brown, E, et al. Distribution of lag-1 alleles and sequence-based types among Legionella pneumophila serogroup 1 clinical and environmental isolates in the United States. J Clin Microbiol 2009;47:25252535.Google Scholar
15. Benitez, AJ, Winchell, JM. Clinical application of a multiplex real-time PCR assay for simultaneous detection of Legionella species, Legionella pneumophila, and Legionella pneumophila serogroup 1. J Clin Microbiol 2013;51:348351.Google Scholar
16. Gaia, V, Fry, NK, Harrison, TG, Peduzzi, R. Sequence-based typing of Legionella pneumophila serogroup 1 offers the potential for true portability in legionellosis outbreak investigation. J Clin Microbiol 2003;41:29322939.Google Scholar
17. Ratzow, S, Gaia, V, Helbig, JH, Fry, NK, Luck, PC. Addition of neuA, the gene encoding N-acylneuraminate cytidylyl transferase, increases the discriminatory ability of the consensus sequence-based scheme for typing Legionella pneumophila serogroup 1 strains. J Clin Microbiol 2007;45:19651968.Google Scholar
18. Kozak-Muiznieks, NA, Lucas, CE, Brown, E, et al. Prevalence of sequence types among clinical and environmental isolates of Legionella pneumophila serogroup 1 in the United States from 1982 to 2012. J Clin Microbiol 2014;52:201211.Google Scholar
19. Wadowsky, RM, Yee, RB, Mezmar, L, Wing, EJ, Dowling, JN. Hot water systems as sources of Legionella pneumophila in hospital and nonhospital plumbing fixtures. Appl Environ Microbiol 1982;43:11041110.Google Scholar
20. Dennis, PJ, Green, D, Jones, BP. A note on the temperature tolerance of Legionella . J Appl Bacteriol 1984;56:349350.Google Scholar
21. Legionella and the prevention of legionellosis. World Health Organization. Geneva, Switzerland: WHO Press; 2007.Google Scholar
22. Helms, CM, Massanari, RM, Wenzel, RP, Pfaller, MA, Moyer, NP, Hall, N. Legionnaires’ disease associated with a hospital water system. A five-year progress report on continuous hyperchlorination. JAMA 1988;259:24232427.Google Scholar
23. Marrie, TJ, MacDonald, S, Clarke, K, Haldane, D. Nosocomial Legionnaires’ disease: lessons from a four-year prospective study. Am J Infect Control 1991;19:7985.Google Scholar
24. Mermel, LA, Josephson, SL, Giorgio, CH, Dempsey, J, Parenteau, S. Association of Legionnaires’ disease with construction: contamination of potable water? Infect Control Hosp Epidemiol 1995;16:7681.Google Scholar
25. Architects TAIo. Guidelines for design and construction of hospital and health care facilities. Dallas, TX: Facility Guidelines Institute; 2001.Google Scholar
26. Stout, JE, Brennen, C, Muder, RR. Legionnaires’ disease in a newly constructed long-term care facility. J Am Geriatr Soc 2000;48:15891592.Google Scholar
27. Garrison, LE, Kunz, JM, Cooley, LA, et al. Vital signs: deficiencies in environmental control identified in outbreaks of Legionnaires’ disease—North America, 2000–2014. MMWR Morb Mortal Wkly Rep 2016;65:576584.Google Scholar
28. Landau, Z, Rezvak, A, Shtalrid, M, Resnitzky, P. Legionnaires’ disease during induction of remission chemotherapy for acute nonlymphocytic leukemia. Leuk Lymphoma 1995;17:189190.Google Scholar
29. Kaya, D, Erginel, S, Metintas, M, Ustuner, Z, Ucgun, I, Ozdemir, N. Pulmonary infections due to Legionella pneumophila in immunocompromised patients. Turk J Med Sci 2001;31:7377.Google Scholar
30. Mandell, LA, Wunderink, RG, Anzueto, A, et al. Infectious Diseases Society of America/American Thoracic Society consensus guidelines on the management of community-acquired pneumonia in adults. Clin Infect Dis 2007;44 Suppl 2:S27S72.Google Scholar
31. Kohler, RB, Winn, WC Jr, Wheat, LJ. Onset and duration of urinary antigen excretion in Legionnaires disease. J Clin Microbiol 1984;20:605607.Google Scholar
32. Sopena, N, Sabria, M, Pedro-Botet, ML, et al. Factors related to persistence of Legionella urinary antigen excretion in patients with Legionnaires’ disease. Eur J Clin Microbiol Infect Dis 2002;21:845848.Google Scholar
33. Higa, F, Fujita, J, Koide, M, Haranaga, S, Tateyama, M. Clinical features of two cases of Legionnaires’ disease with persistence of Legionella urinary antigen excretion. Intern Med 2008;47:173178.Google Scholar
34. Top 10 things every clinician needs to know about legionellosis. Centers for Disease Control and Prevention website. http://www.cdc.gov/legionella/clinicians.html. Published 2013. Accessed February 13, 2015.Google Scholar
35. Salvatorelli, G, Medici, S, Finzi, G, De Lorenzi, S, Quarti, C. Effectiveness of installing an antibacterial filter at water taps to prevent Legionella infections. J Hosp Infect 2005;61:270271.Google Scholar
36. Baron, JL, Peters, T, Shafer, R, MacMurray, B, Stout, JE. Field evaluation of a new point-of-use faucet filter for preventing exposure to Legionella and other waterborne pathogens in health care facilities. Am J Infect Control 2014;42:11931196.Google Scholar
37. Guidelines for preventing health-care-associated pneumonia, 2003 recommendations of the CDC and the Healthcare Infection Control Practices Advisory Committee. Respir Care 2004;49:926–939.Google Scholar
38. Developing a water management program to reduce Legionella growth and spread in buildings: a practical guide to implementing industry standards. Centers for Disease Control and Prevention website. http://www.cdc.gov/legionella/downloads/toolkit.pdf. Published 2016. Accessed June 22, 2016.Google Scholar
39. Murdoch, DR. Diagnosis of Legionella infection. Clin Infect Dis 2003;36:6469.Google Scholar
Figure 0

FIGURE 1 Epidemic curve of healthcare-associated cases of Legionnaires’ disease (n=10) by week of symptom onset. ADPH, Alabama Department of Public Health. 1All cases were reported to the respective local health departments within 1 week of positive test results.

Figure 1

TABLE 1 Characteristics of Legionnaires’ Disease Case Patients (n=10) With Exposure to a Hospital Hematology-Oncology Unit — Alabama, 2014.

Figure 2

FIGURE 2 Probable incubation period (2–10 days prior to symptom onset), exposure to hematology-oncology unit, and positive Legionella test collection date by case patient (n=10).

Figure 3

FIGURE 3 Schematic of the hematology-oncology unit showing the sites of positive environmental sampling results (figure not to scale). Of 27 rooms, 9 were occupied by case patients for at least 1 night; Legionella species were isolated from points-of-use in each of the 4 case patient rooms from which samples were obtained.